Step 6 After power-on, the compressor starts preheating, and the system generates a
compressor preheating alarm. The preheating takes 12 hours. The smart cooling
product cannot be started before the compressor preheating is complete. Choose
Running > Device Details > Compressor to view the remaining preheating time
of the compressor.
Figure 6-7 Remaining compressor preheating time
----End

6.4 Home Screen

The home screen of the display module displays the system status and allows you
to access other function menus.
The information in the screenshots is for reference only. The actual parameters
may vary.
Issue 04 (2022-12-15)
Parameter
Humidity setpoint
Modbus Comm
address
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
After the temperature and humidity
control type and the humidity value
under this type are set, the device
performs regulation based on the
settings.
40%–60% is recommended.
Enter the communication address
planned for the smart cooling product.
The management system
communicates with the smart cooling
product through this address. The
communication addresses of the two
smart cooling products connected to
the same management system must
be different.