4.
Figure 11-5 Removing a condensate pump
Step 4 Install the new condensate pump, reinstall the condensate pump assembly in the
cabinet, connect the hoses, and connect and secure the cables.
Step 5 Install the cover of the condensate pump and close the front door.
Step 6 Power on the device.
Step 7 Install the air filter and close the rear door.
Step 8 After startup, choose Maintenance > Performance Maintenance on the home
screen to access the performance maintenance screen, and clear the runtime of
the condensate pump.
Step 9 Check that the smart cooling product is running properly and no alarm is
generated.
----End
11.6 Replacing a Liquid Level Detector
Prerequisites
●
●
●
Issue 04 (2022-12-15)
Remove the hose clamps from the condensate pump pipe and its body,
remove the hose, and take out the condensate pump.
A liquid level detector needs to be replaced.
A spare liquid level detector of the same model is available and functional.
Tool: Phillips screwdriver