Drainpipe - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
No.
1
2
3
4
Note: No dent or bulge is allowed on the surface after the trap is shaped.

4.2.2.4 Drainpipe

The drainpipe can be connected using a hose or rigid pipe.
Figure 4-11 Connecting a drainpipe
(1) Internal thread connector: BSPP 1/2 inch
(3) Rigid pipe: made of PP-R
(5) Hose clamp
Issue 04 (2022-12-15)
Item
Pipe
Outer
Diameter
Oil trap
22.2 mm
Gas pipe
22.2 mm
inverted trap
Liquid pipe
19.0 mm
inverted trap
Liquid pipe
15.9 mm
inverted trap
Copyright © Huawei Digital Power Technologies Co., Ltd.
Thicknes
Requirement
s
1.2 mm
Inner diameter at the
expanded end of the copper
pipe: 22.4 mm; outer diameter
at the shrunk end: 19.5 mm
1.2 mm
Inner diameters at the two
expanded ends of the copper
pipe: 22.6 mm
1.0 mm
Inner diameters at the two
expanded ends of the copper
pipe: 19.0 mm
1.0 mm
Inner diameters at the two
expanded ends of the copper
pipe: 16.3 mm
(2) Adapter: BSPT 1/2 inch, connected to a
rigid pipe with external threads
(4) Pagoda connector
(6) Hose: inner diameter of 3/4 inch, made of
EPDM or other materials
4 System Installation
60

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a050h4we2Netcol5000- a050h40e2

Table of Contents