Mitsubishi Electric 800 Series Installation Manualline page 22

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

WIRING
l Single-phase 200 V class
FR-E820S-0008(0.1K) to 0030(0.4K)
R/L1
S/L2
Earthing (grounding)
terminal
Power supply
CAUTION
l The power supply cables must be connected to R/L1, S/L2, T/L3. Never connect the power cable to the U, V, W, of the inverter. Doing
so will damage the inverter. (Phase sequence needs not to be matched.)
l Connect the motor to U, V, W. At this time turning on the forward rotation switch (signal) rotates the motor in the clockwise direction
when viewed from the motor shaft. (The phase sequence must be matched.)
l Handling of the wiring cover
(FR-E820-0470(11K) to 0900(22K), FR-E840-0230(11K) to 0440(22K))
For the hook of the wiring cover, cut off the necessary parts using a pair of needle-nose pliers etc.
CAUTION
l Cut off the same number of lugs as wires. If parts where no wire is put through have been cut off (10 mm or more), protective structure
(IEC 60529) becomes an open type (IP00).
16
Jumper
N/-
P/+
PR
M
Motor
FR-E820S-0050(0.75K) to 0110(2.2K)
N/- P/+
Jumper
Jumper
R/L1 S/L2
PR
Power supply
Earthing (grounding)
M
terminal
Motor

Advertisement

Table of Contents
loading

Table of Contents