3
REPLACEMENT OF I/O MODULE
(2) Specifications comparison between A1SX10EU and QX10
Specifications
Number of input points
Isolation method
Rated input voltage
Input voltage distortion
Rated input current
Inrush current
Operating voltage range
Maximum number of
simultaneous input points
On voltage/on current
Off voltage/off current
Input resistance
Off  on
Response
time
On  off
Common terminal
arrangement
Operation indication
External connection
system
Applicable wire size
Applicable solderless
terminal
Current consumption
Dielectric withstand
voltage (between batch
external circuits and
internal circuit)
Insulation resistance
Noise immunity
External dimensions
Weight
*1
Check the specifications of the sensor or switches to connected to the QX10.
*2
The following shows the derating chart.
100
90
80
On
70
ratio
60
50
40
0
3
- 17
A1SX10EU
16 points
Photocoupler
100-120VAC 50/60Hz
Within 5%
Approx. 7mA (120VAC 60Hz)
Maximum 200mA Within 1ms
(132VAC)
85 to 132VAC
(50/60Hz±5%)
Simultaneously on (100%)
80VAC or more/5mA or more
30VAC or less/1.4mA or less
Approx. 18k (60Hz)
Approx. 21k (50Hz)
20ms or less
(100VAC 60Hz)
35ms or less
(100VAC 60Hz)
16 points/common
(common terminal: TB9, TB18)
On indication (LED)
20-point terminal block connector
(M3.57 screws)
2
0.75 to 1.25mm
(16 to 19 AWG)
RAV1.25-3.5
0.05A (typ. all points on)
1780VAC rms/3 cycles (altitude
2,000m (6562ft))
10M or more with an insulation
resistance tester
IEC801-4: 1kV
130(H)34.5(W)93.6(D)mm
0.21kg
(QX10)
120VAC
132VAC
10
20
30
40
50 55
Ambient temperature
: Compatible,
QX10
16 points
Photocoupler
100-120VAC 50/60Hz
Within 5%
Approx. 8mA (100VAC, 60Hz),
Approx. 7mA (100VAC, 50Hz)
Maximum 200mA Within 1ms
(132VAC)
85 to 132VAC
(50/60Hz±3Hz)
*2
Refer to the derating chart.
80VAC or more/5mA or more
(50Hz, 60Hz)
30VAC or less/1.7mA or less
(50Hz, 60Hz)
Approx. 12k (60Hz)
Approx. 15k (50Hz)
15ms or less
(100VAC 50Hz, 60Hz)
20ms or less
(100VAC 50Hz, 60Hz)
16 points/common
(common terminal: TB17)
On indication (LED)
18-point terminal block
(M36 screws)
2
Core: 0.3 to 0.75mm
(outside diameter: 2.8mm or less)
R1.25-3
(Sleeved solderless terminal cannot
be used.)
0.05A (typ. all points on)
1780VAC rms/3 cycles
(altitude 2000m (6562ft))
10M or more with an insulation
resistance tester
• By noise simulator of 1500Vp-p
noise voltage, 1µs noise width,
and 25 to 60Hz noise frequency
• First transient noise IEC61000-4-
4: 1kV
98(H)27.4(W)90(D)mm
0.17kg
: Partially changed, : Incompatible
Compat-
Precautions for replacement
ibility
Use it within the range shown in
the derating chart.
*1
The off current differs.
The input resistance is
*1
reduced.
Wiring change is required.
Wiring space is narrower.

Advertisement