5
REPLACEMENT OF BASE UNIT AND EXTENSION CABLE

5.5.2 Applicable programmable controller

The following modules are mountable to the CPU slot on the AnS size Q series large type base unit.
(The Process CPU, Redundant CPU, and safety CPU are not mountable.)
• Universal model QCPU (including High-speed Universal model QCPU)
The Q00UJCPU cannot be used.
• MELSECNET/H remote I/O module

5.5.3 Modules that cannot be mounted on the AnS size Q series large type base unit

This section describes the modules that cannot be mounted on the AnS size Q series large type base
unit.
(1) Two-slot module
Example
Such as Q64TCRTBW, Q64TCRTBWN, Q64TCTTBW, Q64TCTTBWN, QD70D4,
QD70D8, QJ71LP21S-25, and QJ71GP21S-SX
(2) Module on which the AnS size Q series large type black cover cannot be attached
• Module whose height exceeds 98mm
• Module with a bracket on its top
• A module with a protrusion, such as a connector, on the bottom
• Module on which the Q7BAT-SET has been mounted
Example
Module on which the Q66AD-DG, Q66DA-G, Q68AD-G, Q68RD3-G, Q68TD-G-H02,
Q64AD2DA, QD75M1, QD75MH1, QD75M2, QD75MH2, QD75M4, or QD75MH4 has
been mounted; or the QJ71WS96 on which the Q7BAT-SET has been mounted
A module with a bracket cannot be mounted.
A module with the height exceeding 98mm cannot be mounted.
5
- 19
A module having a projection (such as a connector)
on its bottom cannot be mounted.
A two-slot module cannot be mounted.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-ans/qnas

Table of Contents