REPLACEMENT OF POWER SUPPLY MODULE
(2) Specifications comparison between A1S61PN and Q61SP
Specifications
Input power supply
Input frequency
Input voltage distortion
Max. input apparent
power
Inrush current
5VDC
Rated output
current
24VDC
5VDC
Overcurrent
protection
24VDC
5VDC
Overvoltage
protection
24VDC
Efficiency
Withstand voltage
Noise immunity
Insulation resistance
Power indicator
Fuse
Terminal screw size
Applicable wire size
Applicable solderless
terminal
Applicable tightening
torque
External dimensions
Weight
Allowable momentary
power failure period
Accessory
A1S61PN
100-240VAC+10%-15%
(85 to 264VAC)
±
50/60Hz
5%
Within 5%
105VA
20A within 8ms
5A
5.5A or more
5.5 to 6.5V
65% or more
Between batch inputs and LG and
batch outputs and FG
2830VAC rms/3 cycles (2000m)
• By noise simulator of 1500Vp-p
noise voltage, 1µs noise width,
and 25 to 60Hz noise frequency
• Noise voltage IEC801-4, 2kV
Between batch inputs and LG and
batch outputs and FG
10M or more with the 500VDC
insulation resistance tester
LED indication
(Turns on when 5VDC is output.)
Built-in (unchangeable)
M3.5 7
2
0.75 to 2mm
RAV1.25-3.5, RAV2-3.5
59 to 88N·cm
130(H)  55(W)  93.6(D)mm
0.60kg
Within 20ms
None
: Compatible,
Q61SP
100-240VAC+10%-15%
(85 to 264VAC)
±
50/60Hz
5%
Within 5%
40VA
20A within 8ms
2A
2.2A or more
5.5 to 6.5V
70% or more
Between batch inputs and LG and
batch outputs and FG
2830VAC rms/3 cycles (2000m)
• By noise simulator of 1500Vp-p
noise voltage, 1µs noise width,
and 25 to 60Hz noise frequency
• Noise voltage IEC61000-4-4, 2kV
• Between batch inputs and LG and
batch outputs and FG
• Between all inputs and LG
• Between all outputs and FG
10M or more with the 500VDC
insulation resistance tester
LED indication
(normal: on (green), error: off)
Built-in (unchangeable)
M3.5 screws
2
0.75 to 2mm
RAV1.25-3.5, RAV2-3.5
66 to 89N·cm
98(H)  27.4(W)  104(D)mm
0.18kg
Within 20ms
None
: Partially changed : Incompatible
Compat-
Precautions for replacement
ibility
The Q61SP can be used with the
slim type main base unit only.
Check the current consumption of
entire system.
Although the current value differs,
the rated output is within +10%
difference and the specifications
are the same.
Tighten within the applicable
tightening torque.
Wiring space is narrower.