Mitsubishi Electric MELSEC Q Series Handbook page 152

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
REPLACEMENT OF I/O MODULE
(b) Specifications comparison between A1SJ-56DT (output part) and QY50
Specifications
Number of output points
Isolation method
Output format
Rated load voltage
Operating load voltage
range
Maximum load current
Maximum inrush current
Leakage current at off
Maximum voltage drop at
off
Off  on
Response
time
On  off
Surge suppressor
Common terminal
arrangement
Operation indication
Fuse rating
(breaking capacity)
Fuse blown indication
Voltage
External
power
supply
Current
External connection
system
Applicable wire size
Applicable solderless
terminal
Number of occupied
I/O points
Current consumption
External dimensions
Weight
3
- 99
A1SJ-56DT
(output specifications)
24 points
Photocoupler
Sink type
24VDC
19.2 to 30VDC
(peak voltage 30VDC)
0.5A/point, 4A/common
4A 10ms or less
0.1mA or less
0.9V (typ.) 0.5A
1.5V (MAX.) 0.5A
2ms or less
2ms or less
(resistance load)
Zener diode
8 points/common
(common terminal: TB10, TB20,
TB30)
On indication (LED)
None
24VDC (19.2 to 30VDC)
60mA
(typ. 24VDC for each common)
34-point terminal block connector
2 pieces (M3.56 screws)
2
0.75 to 2mm
R1.25-3.5, R2-3.5
RAV1.25-3.5, RAV2-3.5
128 points
(slot 0: Output 64 points,
slots 1 to 4: Empty 16 points)
0.22A (typ. all points on)
130(H)174.5(W)65.6(D)mm
0.70kg
: Compatible,
QY50
16 points
Photocoupler
Sink type
12-24VDC
10.2 to 28.8VDC
0.5A/point, 4A/common
4A 10ms or less
0.1mA or less
0.2VDC (typ.) 0.5A,
0.3VDC (MAX.) 0.5A
1ms or less
1ms or less
(rated load, resistance load)
Zener diode
16 points/common
(common terminal: TB18)
On indication (LED)
6.7A
(1 fuse/common)
Cannot be changed.
(breaking capacity: 50A)
Available
(LED turns on when a fuse is blown
and a signal is output to the CPU
module.)
12-24VDC (+20/-15%)
(ripple ratio within 5%)
20mA
(24VDC)
18-point terminal block
(M36 screws)
2
Core: 0.3 to 0.75mm
(outside diameter: 2.8mm or less)
R1.25-3
(Sleeved solderless terminal cannot
be used.)
16 points
(I/O assignment: Output 16 points)
0.08A (typ. all points on)
98(H)27.4(W)90(D)mm
0.17kg
: Partially changed, : Incompatible
Compat-
Precautions for replacement
ibility
When 17 or more points are
used, use two QY50 modules.
Voltage exceeding 28.8VDC is
not applicable.
As the number of points per
common is changed to 16, wiring
with a different voltage for each
common is not possible.
The QY50 does not detect fuse
blown unless the external power
is supplied.
Voltage exceeding 28.8VDC is
not applicable.
Wiring change is required.
-
The module configuration differs.
-
Recalculate the current
consumption.
Wiring space is narrower.