Mitsubishi Electric LGH-15RX5 -E Instruction Manual page 7

Hide thumbs Also See for LGH-15RX5 -E:

Advertisement

Two remote controller system with multiple Lossnay units
Remote controller
PZ-60DR-E or
PZ-41SLB-E
● It is also possible to operate two remote controller units when using mul-
tiple Lossnay units.
Interlocking multiple units
When the operation signal is an uncharged a-contact signal
Lossnay
A/C
Power supply
Power supply
Remote controller
Air conditioning
PZ-60DR-E or
unit side remote
PZ-41SLB-E
controller
● Interlocking is possible from multiple air conditioning units, etc.
(excluding pulse input)
(Separately sold parts are necessary depending on the operation signal).
Interlocking/individual combined systems
Interlock settings are possible with the inclusion of a group setting.
(Joint use of the air conditioner remote controller and Lossnay remote
controller is possible.)
Operation settings
Centralized
Indoor unit of
controller
air conditioner
Outdoor
(000)
(01)
unit (51)
MA remote
controller
● Applicable indoor units are C type or later (for use with MA remote con-
troller) models
● Set the different groups of indoor unit of air conditioner and Lossnay unit.
Power supply
Power supply
A/C
A/C
Power supply
Power supply
Air conditioning
Air conditioning
unit side remote
unit side remote
controller
controller
Lossnay (02)
Lossnay remote
controller
(PZ-60DR-E)
Group 1
Group 2
( ) address
Use Lossnay remote controller PZ-60DR-E or PZ-41SLB-E .
(Do not use PZ-52SF-E).
Lossnay transmission connection terminal
Remote controller input terminal
Transmission wires
Setting
Change the setting on the main/sub switch (SW1) on the second
and subsequent Lossnay units to "Sub".
Lossnay
Remote controller
(Main)
(PZ-60DR-E or PZ-41SLB-E)
Power
supply
External
device
Operating switch
for external device
Lossnay (Sub)
Power
TM4
supply
Lossnay (Sub)
TM4
Power
supply
MAX 15 units
Transmission cable
Use Lossnay remote controller PZ-60DR-E .
(Do not use PZ-41SLB-E).
Lossnay transmission connection terminal
M-NET transmission cable
input terminal block
TB5
A
B
S
Shielded wire
M-NET
transmission cable
and PZ-52SF-E
Address Setting
SA1
SA2
10 digit
1 digit
● When the address number has been changed, the data in the memory is
automatically reset.
2
1
PZ-60DR-E
TM4
Main/Sub selection
switch
(SW1)
Power
Main Sub
supply
(Factory setting: main)
First Lossnay
1
2
Connect to
remote
controller
Second
(PZ-60DR-E)
1
2
Lossnay
Connect
to third
Lossnay
Remote controller
input terminal
2
1
PZ-60DR-E
TM4
Transmission wires
Address setting switch
C-7