5.2
Delayed Interlocked Operation
It is possible to delay operation of the Lossnay if an external device is operating. (Energy saving capability.)
<When PZ-41SLB-E is used> (Refer to page C-91, Remote controller to be set)
● Choose from 10, 20, 30, 40, 50, and 60 minute delayed Lossnay operation.
● Delayed operation does not occur if the Lossnay operation was cancelled within the last two hours.
(When turned off for a short time, during a lunch break, for example, if the direction to restart operation is given within two
hours, the Lossnay will restart immediately.)
● If an operation button is pressed on the remote controller while the delay timer is operating, the delayed operation is can-
celled and normal operation begins.
<When PZ-41SLB-E is not used>
Delays Lossnay operation for 30 minutes.when City Multi or Mr.Slim starts operating or when a external device starts operat-
ing. (Refer to page C-74)
5.3
Multiple External Device Operation
(PZ-60DR-E, PZ-41SLB-E, M-NET)
When there are multiple air conditioners or other external devices
Characteristics
Lossnay operates at the same time as
any of the external devices.
System Example
When the Operation Signal is a Uncharged a-contact Level Signal.
(Signal cable between
Lossnay and remote
controller must be more
than 500 m.)
φ 0.65 to 1.2 PVC cable or
2
2
0.3 mm
to 1.25 mm
strand wire.
C-24
Ordered parts
Remote controller
Lossnay
Power supply
Lossnay Remote
controller
PZ-60DR-E
Uncharged a-contact
Uncharged a-contact
Indoor unit of
Indoor unit of
air conditioner 1
air conditioner 2
Power supply
Indoor unit
Indoor unit
remote controller
remote controller
* Illustration shows an example when using PZ-60DR-E
Notes
• Can receive level signal, uncharged
a-contact external signals.
• If the external device is a pulse sig-
nal or charged signal, multiple con-
nections cannot be made.
Uncharged a-contact
Indoor unit of
air conditioner 4
Power supply
Power supply
Indoor unit
remote controller

Advertisement