8. M-NET System Designs
8.1
Address Definitions
An address is a unique number used to identify each indoor unit of air conditioner and controller.
Unit
Indoor unit of air conditioner
Lossnay unit
Outdoor unit
BC controller
(Main)
BC controller
(Sub)
PZ-52SF-E
M-NET, LOSSNAY
Remote controller
(Main)
PZ-52SF-E
M-NET, LOSSNAY
Remote controller
(Sub)
Group remote
controller
System remote
controller
ON/OFF remote
controller
Schedule timer
AG-150A, G50-A
LMAP02-E
Note:
● There is no need to set the address unless the Lossnay is connected to the M-NET transmission cable.
Address setting
01 to 50
51 to 99, 100
52 to 99, 100
53 to 99, 100
1
101 to 150
Fixed
1
151 to 199, 200
Fixed
2
201 to 250
Fixed
0
000, 201 to 250
100
0
202 to 250
100
000, 201 to 250
Set up on display
2
201 to 250
Fixed
Example
Use the smallest address within the same group of
indoor units. Make the address of the indoor units
0
0
connected to the sub BC controller larger than the
address of indoor units connected to the main BC
10
1
controller.
The smallest address of indoor unit in same refriger-
0
0
ant system +50.
*The address automatically becomes "100" if it is set
10
1
as "01 to 50".
The address of outdoor unit +1.
*Choose another address between 01 and 50 if two
0
0
address overlap.
*The address automatically becomes "100" if it is set
10
1
as "01 to 50".
0
0
Smallest address within the indoor units connected
to the BC controller (Sub) plus 50.
10
1
The smallest address of indoor unit in the group +
0
0
100.
*The place of "100" is fixed to "1".
10
1
The address of main remote controller +50.
0
0
*The address automatically becomes "200" if it is
set as "00".
10
1
0
0
The smallest group No. to be managed +200.
10
1
0
0
10
1
0
0
10
1
0
0
10
1
Note
C-37