10.2.2 Troubleshooting 2
l An error code displays on the remote controller.
l The LED on the Lossnay circuit board is blinking or lit up.
An error code displayed on the remote controller (PZ-60DR-E, PZ-41SLB-E, PZ-52SF-E) or the M-NET con-
troller, and blinking or illumination of LED1 (green) or LED2 (red) on the circuit board shows the type of error.
The LED blink interval is 0.25 seconds for both on and off. The display duration is approximately 5 seconds.
Checklist of error codes displayed on the PZ-60DR-E (when not using M-NET) or PZ-41SLB-E, and LED displays (Table2-1)
LED1
LED2
Error code
(green)
(red)
LC 6608
RC6608
SRC 6608
RC 6201,6202
SRC 6201,6202
LC 0900
SLC 0900
LC 3126
8
blinks
SLC 3126
C-52
0.25S 0.25S 0.25S
ON
OFF
Error display example: (Two blinks)
Error
« When using multiple Lossnay units, the
Lossnay
communi-
Main/Sub setting has not been made
cation
for the second unit and following units.
error
« Multiple transmission cables are
wired using multi core cables.
« Transmission cable and power cable
are too close.
« Transmission cable is not securely connected.
« The length of the transmission cable
wiring is longer than specified
(longer than 500 m).
« Multiple transmission cables are
Communica
tion error
wired using multi core cables.
between
remote con-
« Transmission cable and power sup-
trollers
ply cable are too close.
(when two
« Transmission cable is not securely connected.
remote con-
« The length of the transmission cable
trollers are
wiring is longer than specified
connected)
(longer than 500 m).
« The remote controller has broken
Remote
controller
down.
error
« Trial operation switch on the
Lossnay
trial opera-
Lossnay circuit board (SW2-1) is set
tion
to ON.
« When the TM3 6, 7 output setting
External
device
switch (SW5-6) is ON, the following
error
conditions are applied.
• OA temperature is still -10°C or lower,
60 minutes after the output started
• OA temperature is 15°C or higher with-
in 15 minutes after the output started
• OA temperature is 70°C or higher
5S
Cause
Action
« Turn off the main power supply and set the
Main/Sub selection switch (SW1) (first unit to
"Main", second and following units to "Sub").
« Using suitable cables, wire the
transmission cables so that they are
separated from one another.
« Wire the transmission cable at least 5
cm away from the power supply cable.
« Check the transmission cable connection.
« Check the length of the transmission
cable wiring.
« Using suitable cables, wire the
transmission cables so that they are
separated from one another.
« Wire the transmission cable at least 5
cm away from the power supply cable.
« Check the transmission cable connection.
« Check the length of the transmission
cable wiring.
« Replace the remote controller.
« Check the trial operation switch.
(Refer to page C-76)
« When external devices are connect-
ed, check the external devices.
« When external devices are not con-
nected, check the TM3 6, 7 output
setting switch (SW5-6). (Refer to
page C-75)