4.2
System Examples
One Lossnay with one remote controller
Lossnay
Non-polar
Two wires
Remote controller
PZ-60DR-E or PZ-41SLB-E
● A simple system in which Lossnay is operated
independently with one remote controller.
Operating with Mr. Slim
Remote
controller
● The Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E) cannot be
used with this system.
● Use MA remote controller of Mr.Slim for switching Lossnay ON/OFF or
the fan speed.
● The ventilation mode is "automatic ventilation".
Air conditioning device and system control
Outdoor unit
Lossnay
Indoor
unit
MA remote controller
Interlock-Group 1
Refrigerant 1
Outdoor unit
Lossnay
Indoor
unit
MA remote
controller
Interlock-Group 1
● One Lossnay can be interlocked with 16 indoor units. In addition, PZ-60DR-E (non M-NET) can be connected for each Lossnay units.
Centralized controller
● Detailed control such as start/stop, fan speed Extra-Low and ventilation mode control is possible from the Lossnay remote controller PZ-60DR-E.
● PZ-52SF-E (M-NET remote controller) can be used instead of PZ-60DR-E. However, function is limited and connecting position is different.
● Start/stop, fan speed and ventilation mode control is possible from the centralized controller.
● Controller can set up the group including maximum of 16 indoor or Lossnay units.
C-6
Multiple Lossnay units with one remote controller
Non-polar
Two wires
Power supply
Remote
controller
PZ-60DR-E or
PZ-41SLB-E
● Up to 15 Lossnay units can be controlled at
one time with one remote controller.
Lossnay
Power supply
Power supply
Mr. Slim
(indoor unit)
Indoor
Lossnay
Indoor
Indoor
unit
unit
unit
MA remote controller
MA remote controller
Interlock-Group 2
Interlock-Group 3
Lossnay
Indoor
unit
MA remote controller
Interlock-Group 2
Lossnay
Lossnay
Power
supply
unit
Lossnay
remote controller
PZ-60DR-E
Group 1
Group 2
Lossnay
(Main)
Power supply
Lossnay
(Sub)
Power supply
Operating with an external device
Non-polar
Two wires
Remote controller
PZ-60DR-E or
PZ-41SLB-E
Indoor unit
Remote controller
● Lossnay operation will be performed via the external device.
● Level signal or pulse signal input (12V DC, 24V DC, uncharged a-con-
tact) is possible.
Lossnay
Lossnay
Indoor
Indoor
unit
unit
MA remote controller
MA remote controller
Interlock-Group 4
Interlock-Group 5
Refrigerant 2
Outdoor unit
Lossnay
Indoor
Indoor unit
Indoor
unit
unit
MA remotecontroller
Interlock-Group 3
Lossnay Lossnay
Lossnay
Lossnay
Lossnay
remote controller
PZ-60DR-E
Group 3
Group 4
Two remote controller system with one Lossnay
Non-polar
Two wires
Lossnay
Power supply
Remote controller
PZ-60DR-E or PZ-41SLB-E
● Lossnay can be controlled from two remote
locations.
● The remote controller gives priority to the last
operation function request.
● Selection of inter-
Lossnay
locked operation
mode is possible.
● Delayed start inter-
Power supply
locked operation is
possible.
Power supply
・ ・ ・Group setting
Interlocked
・ ・ ・
operation setting
Lossnay
Lossnay
Lossnay
Lossnay
remote controller
remote controller
PZ-60DR-E
PZ-60DR-E
Group 5