System Examples: 2
A sophisticated system including City Multi can also be configured.
Centralized controller ( 000 )
M-MET
Power
supply
unit
Outdoor unit
( 059 )
M-MET
Indoor unit
(009)
ME
remote controller
Group6
Group 1
: One Lossnay unit and one Lossnay remote controller.
Group 2
: Without Lossnay remote controller.
Group 3
: Multiple Lossnay units and one Lossnay remote controller.
Group 4
: One Lossnay unit and two Lossnay remote controllers.
Group 5
: Multiple Lossnay units and two Lossnay remote controllers.
Group 6
: One Lossnay unit is interlocked to one indoor unit. (PZ-60DR-E is not necessary)
Group 7
: One Lossnay unit is interlocked to multiple indoor units. (PZ-60DR-E is not necessary)
Group 8
: Multiple Lossnay units connected to an indoor unit transmission cable
and one Lossnay remote controller.
Group 9
: Without Lossnay units.
Note:
● Hard wire connection from PZ-60DR-E is required independent from M-NET line. If change the Group setting in the future, it
is required to change the wiring of PZ-60DR-E.
● Do not use Lossnay remote controller PZ-41SLB-E.
C-20
Lossnay
Lossnay
(001)
(002)
Lossnay remote
controller PZ-60DR-E
Group1
Group2
Lossnay
Indoor unit
(010)
(011)
( 109 )
ME
Lossnay remote
remote controller
controller PZ-60DR-E
Group7
Lossnay
Lossnay
Lossnay
(003)
(004)
(005)
Lossnay remote
controller PZ-60DR-E
Group3
Lossnay
Indoor unit
(013)
(012)
( 111 )
Lossnay remote
controller PZ-60DR-E
Lossnay
(006)
Lossnay remote
controller PZ-60DR-E
Group4
Lossnay
Lossnay
Indoor unit
(014)
(015)
(016)
( 116 )
Lossnay remote
controller PZ-60DR-E
Group8
Group9
( ) address
Lossnay
Lossnay(008)
(007)
Lossnay remote
controller PZ-60DR-E
Group5
ME