REPLACEMENT OF MELSECNET (II) AND /B (PLC TO PLC NETWORK)
(b) MELSECNET/H control station
Each of the MELSECNET II first and second half settings correspond to [Setting1] and [Setting2] set
according to the "Station inherent parameters" on MELSECNET/H.
Points when replacing the first and second half of MELSECNET II
MELSECNET sequence programs can be re-used more efficiently by using the station inherent parameters of MELSECNET/H.
The followings describe the points when setting station inherent parameters.
• Set station inherent parameters to all stations.
1) Network parameter
The network parameter settings of the MELSECNET/H control station (Q06UDVCPU) are the
same as the parameters when replaced with the MELSECNET mode.
Network parameter setting (Q06UDVCPU: MELSECNET/H control station)
2) Network range assignment parameter
Set the total number of points in the first half and second half for the common parameters.
Network range assignment (Q06UDVCPU: MELSECNET/H control station)
2
- 19