Switch Setting Comparisons - Mitsubishi Electric MELSEC-A Series Manual

Network modules
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

5
REPLACEMENT OF THE MELSECNET/10 (REMOTE I/O NETWORK)

5.1.4 Switch setting comparisons

(1) Switch settings comparisons of remote master station
Switch name
A/AnS/QnA/QnAS series
MELSECNET/10 module
Network No.
Sets the network No.
setting switch
Sets the mode.
<Setting range>
0: Online
2: Offline
3: Loop test (forward loop)
4: Loop test (reverse loop)
5: Station-to-station test
(master station)
Mode setting
6: Station-to-station test
switch
(slave station)
7: Self-loopback test
8: Internal self-loopback test
9: H/W test
D: Network No. check
E: Group No. check
F: Station No. check
Condition
Sets the operation conditions.
setting switch
*1
Group No. check is not used on the remote I/O network.
5
- 22
Description
Q series
MELSECNET/H module
-
[Using QJ71LP21-25 and
QJ71LP21S-25]
Sets the mode.
<Setting range>
0: Online (10Mbps)
1: Self-loopback test (10Mbps)
2: Internal self-loopback test
(10Mbps)
3: Hardware test (10Mbps)
4: Online (25Mbps)
5: Self-loopback test (25Mbps)
6: Internal self-loopback test
(25Mbps)
7: Hardware test (25Mbps)
[Using QJ71LP21G and
QJ71BR11]
Sets the mode.
*1
<Setting range>
0: Online
1: Self-loopback test
2: Internal self-loopback test
3: Hardware test
-
: Compatible,
: Partial change required, × : Incompatible
Compat-
Precautions for replacement
ibility
• Set in GX Works2 or GX
Developer network parameters.
• Network No.240 to No.255
cannot be set.
Alternate them with unused
network Nos.
• Set offline and loop test in GX
Works2 or GX Developer
network parameters.
• Substitute the forward loop/
reverse loop test for the station-
to-station test.
• Check network No., group No.
and station No. in GX Works2 or
GX Developer network
diagnostics (host information).
Set in GX Works2 or GX
Developer network parameters.

Advertisement

Table of Contents
loading

Table of Contents