Mitsubishi Electric MELSEC-A Series Manual page 176

Network modules
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

5
REPLACEMENT OF THE MELSECNET/10 (REMOTE I/O NETWORK)
5) Performance comparison of AJ71BR11/A1SJ71BR11/AJ71QBR11/A1SJ71QBR11 and
QJ71BR11
Item
LX/LY
8192 points
Maximum number
of link points per
LB
8192 points
network
LW
8192 points
<Remote master
station  remote I/O
station>
{(LY + LB) 8 + (2 ×
Maximum number of link
LW)}
points per station
<Remote I/O station
 remote master
station>
{(LY + LB) 8 + (2 ×
LW)}
Communication speed
10Mbps
Communication method
Token bus method
Synchronous type
Frame synchronization method
Encoding method
Manchester code
Transmission method
Single bus
Transmission format
HDLC standards (frame format)
255 (Total number of
Maximum number of
PLC to PLC networks
networks
and remote I/O
networks)
Number of stations connected
33 stations (Remote master station: 1, remote I/O station: 32)
in one network
Applicable cable
3C-2V, 5C-2V, 5C-FB
3C-2V: 300m
Overall distance
5C-2V, 5C-FB: 500m
3C-2V: 300m
Distance between stations
5C-2V, 5C-FB: 500m
Error control system
CRC(X
• Diagnostic function for checking local link lines
RAS function
• Abnormal detection using link special relays and link special registers
• Network monitoring and various diagnostic functions
• Monitor, program up/download with
peripheral device
Transient transmission
• Dedicated link instruction
• Available for Intelligent function module
(only AJ71QBR11/A1SJ71QBR11)
Number of occupied I/O
32 points per slot (I/O assignment: special 32
points
points)
Remote master station  remote sub-master station, remote I/O station: 8192 points
*1
Remote sub-master station, remote I/O station  remote master station: 8192 points
*2
The remote master station includes the multiplexed remote master station and multiplexed remote sub-master station.
*3
For the multiplexed remote I/O network, one station in 32 stations of the remote I/O station is used for the multiplexed
remote sub-master station.
5
- 10
Specifications
AJ71BR11
AJ71QBR11
A1SJ71BR11
A1SJ71QBR11
<Remote master station  remote I/O station>
{(LY + LB) 8 + (2 × LW)}
<Remote I/O station  remote master station>
1600 bytes
{(LY + LB) 8 + (2 × LW)}
<Multiplexed remote master station  multiplexed
remote sub-master station>
{(LY + LB)  8 + (2 × LW)}
1600 bytes
239 (Total number of PLC to PLC networks and
remote I/O networks)
16
12
5
+ X
+ X
+ 1) and retry by a time over
: Compatible,
Compatibility
QJ71BR11
*1
16384 points
*1
16384 points
*2
1600 bytes
*2
1600 bytes
2000 bytes
*3
• 1:1 communication
(Monitor, program up/
download)
• Dedicated link instruction
32 points per slot (I/O
assignment: intelli. 32 points)
: Partial change required, × : Incompatible
Precautions for replacement
Network No.240 to No.250 cannot
be set. Alternate them with
unused network No.
For comparison of dedicated link
instruction, refer to Section 5.1.7.