7
ONLINE MODULE CHANGE
7 - 31
(b)
If the saved buffer memory contents are not yet prerecorded, record them
in the following procedure.
1)
Make Pass data classification setting (buffer memory address 200:
Un\G200)
2)
Turn Operating condition setting request (Y9) from off to on.
3)
Compare the offset/gain values of Industrial shipment settings and
User range settings (buffer memory address 202 to 233: Un\G202 to
Un\G233) with the range reference table. Refer to Section 7.4 for the

range reference table.

4)
If the values are proper, record the offset/gain values of Pass data
classification setting
settings.
1: The Q68ADV/Q68ADI does not require the setting and recording of
Pass data classification setting.
POINT
If the buffer memory values compared with the reference table are not proper, save
and restoration of the user range cannot be executed.
Before executing module control resumption, follow the flowchart in Section 4.6 and
make offset/gain setting in the device test of GX Developer.
Perform mode switching by making the setting of Mode switching setting (buffer
memory address 158, 159: Un\G158, Un\G159) and turning Operating condition
setting request (Y9) from off to on.
Note that if module control is resumed without offset/gain setting being made,
operation will be performed with the default values.
(2) Dismounting of module
(a)
After choosing [Diagnosis] - [Online module change] on GX Developer to
enter the "Online module change" mode, double-click the module to be
changed online to display the "Online module change" dialog box.
1
.
1
, Industrial shipment settings and User range
MELSEC-Q
7 - 31