Mitsubishi Electric Melsec Q Series User Manual page 129

Analog-digital converter module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

7
ONLINE MODULE CHANGE
7 - 10
(2) Dismounting of module
(a)
Take the following steps to disable the conversion:
1)
Set A/D conversion enable/disable setting (buffer memory address 0:
Un\G0) to All channel conversion disable (FH).
2)
Turn Operating condition setting request (Y9) from off to on to stop the
conversion.
3)
Operating condition setting completed flag (X9) turns off from on.
4)
Check that A/D conversion completed flag (buffer memory address
10: Un\G10) is in a status of Conversion stop (0H).
5)
Turn Operating condition setting request (Y9) from on to off.
MELSEC-Q
7 - 10

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Melsec q64adMelsec q68advMelsec q68adi

Table of Contents