2. DETAILS OF MIGRATION FROM Q17nCPUN(-T) TO RnMTCPU
(Continued)
Models
Q173CPUN(-T)
Items
Output enable/disable bit,
Limit output data
Shared CPU
memory
[Self-diagnostic error code]
• 10000: M2039 OFF
• Less than 10000:
Cancelling errors of
M9060 OFF→ ON
Multiple CPU
(The error code needs to be
stored to the special register of
D9060.)
Motion CPU-specific errors
→"10000" is stored in the
diagnostic error (D9008).
Self-diagnostic
At this time, the self-diagnostic
errors
error flag (M9008) and the
diagnostic error flag (M9010) do
not turn ON.
Motion SFC error
It depends on the error whether
detection flag
M2039 is turned ON or not.
(M2039)
Battery error check
of Motion CPU
Peripheral I/F
Servo system
network
Limit switch output
function
Mark detection
function
RUN/STOP
Q172CPUN(-T)
Forced output bit
H0 to HFFF (4096 words)
Provided
USB/RS232/SSCNET
SSCNET
Up to 32 points
Not available
RUN/STOP switch
R32MTCPU
R16MTCPU
Forced OFF bit,
Forced ON bit
U3E \G0 to U3E \G2097151
(2097152 words)
SM50 ON
• All errors can be cancelled.
• After cancelling errors,
SM50 turns OFF automatically.
All errors are assigned to the
self-diagnostic error codes.
When an error occurs, an error code
is set in SD0, and then SM0 and SM1
turns ON.
None
(integrated into the self-diagnostic
errors)
None
(Battery-less)
USB/Ethernet
(via PLC CPU)
/
PERIPHERAL I/F
(Motion CPU)
SSCNETIII/H or SSCNETIII
Up to 64 points
UP to 64 settings
RUN/STOP switch,
remote RUN/STOP, RUN contact
2 - 7
Points for migration
The setting of "Output enable/disable
bit" and "Forced output bit" in
Q17nCPUN(-T) are respectively
diverted as "Forced OFF bit" and
"Forced ON bit" in RnMTCPU.
The program can be diverted as it is.
If MULTW /MULTR instructions are
used for writing/reading of data to/from
the shared memory, review the
program. (Refer to section 2.2(6).)
For details of RnMTCPU errors, refer to
section 2.2(5).
Use a compatible I/F to communicate
with peripheral devices.
If PC link communication is used,
replace it with USB communication.
In that case, replace the existing cable
with the A-miniB USB cable as well.
►If M2000, M3072, or D704 is directly
operated in the program to switch the
RUN/STOP status, revise the
program. (Refer to section 2.2(7).)