■Recording buffer batch saving mode
The recording buffer batch saving mode is a mode for saving all data accumulated in the recording buffer when selecting "File
Saving Trigger Only" for the recording method.
When this mode is enabled and a file saving trigger is satisfied, all data accumulated in the recording buffer is saved.
This allows data in a period before a set saving period before trigger to be saved.
(1)
(2)
(a)
(b)
(c)
(d)
(1) File saving trigger
(2) Accumulating data
(3) Time
(a) Saving period before trigger
(b) Saving period after trigger
(c) Period during which data is accumulated in the recording buffer
(d) Period during which data is actually saved
The recording buffer batch saving mode can be enabled or disabled in the following buffer memories of a recorder module or
in the "Recording Status Detailed Information" screen of GX Works3. (Page 109 Recording operation specification area
(Un\G4000 to 4799), Page 67 Recording Status Detailed Information Screen)
• Setting No.1: 'Recording buffer batch saving mode' (Un\G4001)
• Setting No.2: 'Recording buffer batch saving mode' (Un\G4101)
• Setting No.3: 'Recording buffer batch saving mode' (Un\G4201)