Mitsubishi Electric MELSEC iQ-R Series User Manual page 111

System recorder user's manual (application)
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Recording operation specification area (Un\G4000 to 4799)
File saving triggers for recording, the recording buffer batch saving mode, and data values added to save folder names can be
checked.
Buffer memory name
Recording operation
Recording buffer batch
specification 1
saving mode
Folder name additional data
1
Folder name additional data
2
File saving trigger
Recording operation specification 2 to 4
■Recording buffer batch saving mode (Un\G4001)
Use this to specify the recording buffer batch saving mode. (Page 39 Recording buffer batch saving mode)
A value when a file saving trigger is satisfied will be valid.
'0' (not use the batch saving mode) is stored at either of the following timings:
• The power is turned ON or a CPU module is reset.
• The operating status switches to 'operating' after writing a recording setting.
■Folder name additional data 1 (Un\G4002 to 4003)/folder name additional data 2 (Un\G4004 to
4005)
Use these to specify data added to a recording file save folder name. (Page 32 Recording file)
When setting "DATA1" or "DATA2" as additional information for a folder name, a value in this buffer memory is added to the
folder name.
A value when a file saving trigger is satisfied will be valid.
A value is cleared to the initial value (0) at either of the following timings:
• The power is turned ON or a CPU module is reset.
• The operating status switches to 'operating' after writing a recording setting.
■File saving trigger (Un\G4007)
Use this for file saving triggers.
It can be used in bit units.
A condition number is added to each bit as follows:
Recording setting No.1: Un\G4007
Recording setting No.2: Un\G4107
Recording setting No.3: Un\G4207
Recording setting No.4: Un\G4307
A value is cleared to the initial value (OFF) at either of the following timings:
• A recorder module is started.
• The operating status switches to 'operating' after writing a recording setting.
Address
Un\G4001
Un\G4002 to 4003
Un\G4004 to 4005
Un\G4007
Un\G4100 to 4399
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
16
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
Description
Use this to specify the recording buffer batch saving mode.
When enabling this mode, '1' (ON) is stored.
0: Not use the batch saving mode (OFF)
1: Use the batch saving mode (ON)
Data 1 added to a recording file save folder name.
Use these when specifying "DATA1" as additional information for a recording
file save folder name.
Data 2 added to a recording file save folder name.
Use these when specifying "DATA2" as additional information for a recording
file save folder name.
Use this for file saving triggers.
Details are the same as recording operation specification 1.
6 RECORDER MODULE (DETAILED SPECIFICATIONS)
109
6.4 Buffer Memory
6

Advertisement

Table of Contents
loading