Power Loss Ridethru (Pwrloss Ridethru); Power Loss Stop (Pwrloss Stop) - GE AV-300i User Manual

Hide thumbs Also See for AV-300i:
Table of Contents

Advertisement

1.11.2.1 Power Loss Ridethru (Pwrloss Ridethru)

When the DC link voltage reaches the starting threshold, the function gets active.
The DC link setpoint is set with a value higher than 12% as compared to the Undervoltage threshold.
The PI regulator controls a negative torque current (recovery) in order to keep the DC link at a constant level.
When the Mains voltage is restored, the system allows a delay on the line speed with the set acceleration time.
Description:
STOP OPTION
STOP OPTION
Pwrloss ridethru cfg
PLR P Gain
PLR I Gain
Pwrloss ridethru mon
PLR active

1.11.2.2 Power Loss Stop (Pwrloss Stop)

Through the PSL mains st src source, the function allows the selection of the command signal, which can state
the Mains recovery (for example via a programmed digital input). The aim is to restart the motor before it reaches
a Speed 0. In the configurations it is possible to set the gain of the internal PI regulator, the DC link reference
threshold with PLS Vdc ref, the torque current limit with PLS curr lim and with PLS timeout a maximum period
after which no automatic restart is possible.
Description:
STOP OPTION
STOP OPTION
Pwr loss stop src
Ch.1
120
GEH-6641E
Power loss
ctrlPOWER LOSS CTRL
Pwrloss ridethru
Pwrloss ride cfg
PLR P Gain
PLR I Gain
Pwrloss ride mon
PLR active
SAVE PERAMETERS
Proportional gain in A/V
Integral gain in A/V/s
It states the function state
Power loss ctrl
Pwrloss stop
Pwrloss stop src
PLS mains st src
Pwrloss stop cfg
PLS P gain
PLS I gain
PLS Vdc ref
PLS curr lim
PLS timeout
Pwrloss stop mon
PLS active
SAVE PERAMETERS
—————— Function Description ——————

Hide quick links:

Advertisement

Table of Contents
loading