At power up, the power converter firing and Ramp/speed regulation may be initiated if Terminal Enable and
Terminal Start/Stop are asserted (driven high).
Once Terminal Enable is asserted, no actuation occurrs until the Terminal Start/Stop is asserted. When this
occurs, the power converter firing is initiated, Motor magnetization sequence is executed, then Ramp and speed
regulation are unlocked.
When terminal Start/Stop is negated, the drive is stopped, and after the programmed delay power converter firing
is terminated.
Negating Terminal Enable will terminate converter firing at any time, and the motor will coast to a stop.
After a power fault, if Terminal enable and Terminal Start/Stop do not change, the drive will restart at power up.
Parameter description
Command select
En/Disable mode
Dig Enable src
Term StrStp src
Dig StrStp src
Term Start src
Term Stop src
FStop src
Jog cmd src
Jog invers src
AV-300i Version 2 User's Guide

Table 1.5.3.4-1: Example Setup for Unmanned Installation

Index
Value
4002
"Terminal level"
4004
"Stop/FS & Spd=0"
0156
Do not care
0153
"DI 1 monitor"
0157
Do not care
9210
Do not care
9211
Do not care
0154
"NULL"
"NULL"
8015
8018
"NULL"
—————— Function Description ——————
Comments
This source bypassed (AND logic)
Tie Start/Stop signal to terminal 13
This source not used
This source not used
This source not used
Fast stop not used
Jog from the keyboard
Jog inversion from the keyboard
TAV35341
Ch.1
65