8.4.7 Replacing a Power Distribution Monitoring Board

Prerequisites
Procedure
Step 1 Loosen the two bolts on the power distribution detection module.
Step 2 Open the two crowbars on the power distribution detection module.
Step 3 Gently pull out the power distribution detection module.
Figure 8-21 Replacing the power distribution detection module
Step 4 Install a new power distribution detection module.
Step 5 Close the two crowbars and tighten the two bolts on the power distribution detection module
in sequence.
----End
Issue 07 (2019-04-15)
Tools required: an electrical tester pen, a pair of insulation gloves, a Phillips screwdriver,
the PDC door key, a multimeter, and a step ladder.
Materials required: a spare power distribution detection module of the same model is
available and functional.