Huawei PDU8000 User Manual page 18

Modular integrated pdc v1.0
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Integrated PDC V1.0
User Manual
Item
Monitoring
function
Certification
compliance
Table 3-2 Input circuit breaker derating
Type
Single input
Dual inputs
Issue 07 (2019-04-15)
IT power distribution
input mode
Air conditioner power
distribution input
mode
Output switch (for
standard
configuration)
Lighting switch
Surge protection
Detection
Communication mode
current transformer (CE) and China Compulsory Certification (CCC)
Circuit Breaker Capacity
250 A
160 A
250 A
Copyright © Huawei Technologies Co., Ltd.
Specifications
160/250
One 3-pole 160 A MCCB input
One 3-pole 250 A MCCB input
Two 3-pole 160 A MCCB inputs
Two 3-pole 250 A MCCB inputs
One 3-pole 160 A MCCB input
One 3-pole 250 A MCCB input
Two 3-pole 160 A MCCB inputs
Two 3-pole 250 A MCCB inputs
IT power distribution branch: a maximum
of 48 branches (single-phase), a maximum
40 A circuit breaker for each branch
Air conditioner power distribution branch:
a maximum of 16 branches (three-phase), a
maximum 63 A circuit breaker for each
branch
(Optional) Branch temperature monitoring,
Hot-Swap Circuit Breaker
Air conditioner two inputs: one 1-pole 10 A x
6
Air conditioner one input: one 1-pole 10 A x 3
Level C. Nominal discharge current In (8/20
µs) = 20 kA, maximum discharge current Imax
(8/20 µs) = 40 kA; voltage protection level Up
(20 kA, 8/20 μs) ≤ 1.8 kV (L-N)/≤ 1.0 kV
(N-PE)
Three-phase input voltage, current, frequency,
active power, reactive power, electric energy,
power factor, and temperature
Supports the Modbus TCP protocol and
Modbus RTU protocol.
Derating Coefficient
0.9
0.9
0.9