Huawei PDU8000 User Manual page 46

Modular integrated pdc v1.0
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Integrated PDC V1.0
User Manual
Table 5-4 Power cable specifications
Port
Descriptio
n
Power input
(L/N)
Power input
(PE)
AC output
(L)
AC output
(N/PE)
Cable Routing Description
Figure 5-21 Cable holes on the top of the PDC
(1) Signal cable hole
(3) Output power cable hole
Issue 07 (2019-04-15)
If the wire bushings cannot be used or are missing, seal the cable inlet and outlet holes
with firestop putty.
Table 5-4 lists the terminal specifications for cables in the PDC. Connect cables to the
corresponding terminals on the rack power distribution unit.
Rated
Current (A)
160
250
160
250
6–40
6–40
YJV5 cables are recommended. The conductor working temperature is 90º C, and the ambient
temperature is 40º C.
Copyright © Huawei Technologies Co., Ltd.
Terminal/Bolt
Cable
Specifications
Diameter
(mm
M10
50
M12
95
M10
25
M10
50
Cord end
6
terminal
M6
6
(2) Input power cable hole
(4) Ground cable hole
5 Installation Guide
Recommended
Torque (N· m)
)
2
27
47
27
27
1.6
4.9
39

Advertisement

Table of Contents
loading