Pulse Train Mode; Function; Introduction - Siemens ET 200SP Manual

Technology module tm pulse 2x24v
Hide thumbs Also See for ET 200SP:
Table of Contents

Advertisement

4.3

Pulse train mode

4.3.1

Function

4.3.1.1

Introduction

In this operating mode, the respective channel of the technology module outputs a number of
pulses with the configured period duration, duty cycle and On delay. You specify the number
of pulses via the control interface.
Starting the output sequence
In order to output the output sequence at the digital output DQn.A, the TM_CTRL_DQ control
bit (Page 126) must be set. To start the output sequence using the software enable, you set
the SW_ENABLE control bit (Page 73). The STS_SW_ENABLE feedback bit indicates that
the software enable in the technology module is active.
You can additionally use the hardware enable via the respective digital input DIn.0. You can
configure an input delay for DIn.0.
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Configuring/address space
4.3 Pulse train mode