4.5.1.2

Frequency

You set the output frequency in the control interface using OUTPUT_VALUE as floating point
number (REAL). The value range is dependent on whether or not the high-speed output
function (Page 98) is being used:
High-speed output
Activated
Deactivated
A changed frequency takes effect with the next rising edge at DQn.A.
Accuracy
The output sequence is output with an accuracy of ±100 ppm at DQn.A.
4.5.1.3

On delay

You set the On delay from 0 s to 85 s with a precision of 1 µs in the hardware configuration.
In addition, you can change the On delay via the control interface by entering a new value in
SLOT as an integer (UDINT). In so doing, you use the MODE_SLOT control bit to choose
whether you want to apply a change once or cyclically:
MODE_SLOT = 0
MODE_SLOT = 1
You can find additional information under Handling of the SLOT parameters (Page 139).
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Value range of
OUTPUT_VALUE
0.02 to 100000
0.02 to 10000
One-time change:
As soon as you write the value 2
value from SLOT is applied once as the On delay and kept until the next
change.
A change via SLOT takes effect at the next output sequence. An active
output sequence is not affected by the change.
Cyclic change:
When you write the value 18
value from SLOT in each case is applied cyclically as the On delay.
A change via SLOT takes effect at the next output sequence. An active
output sequence is not affected by the change.
Configuring/address space
4.5 Frequency output mode
Value range of the frequency
0.02 Hz to 100000 Hz
= 0.02 Hz to 100 kHz
0.02 Hz to 10000 Hz
= 0.02 Hz to 10 kHz
in the corresponding output byte, the
D
in the corresponding output byte, the current
D
97