Configuring/address space
4.1
Pulse output (single pulse) mode
4.1.1
Function
4.1.1.1
Introduction
In this operating mode, the respective channel of the technology module outputs a single
pulse with the configured On delay and the pulse duration specified via the control interface.
4.1.1.2
Output sequence
Starting the output sequence
In order to output the output sequence at digital output DQn.A, the TM_CTRL_DQ control bit
(Page 126) must be set. To start the output sequence using the software enable, you set the
SW_ENABLE control bit (Page 29). The STS_SW_ENABLE feedback bit (Page 32) indicates
that the software enable in the technology module is active.
You can additionally use the hardware enable via the respective digital input DIn.0. You can
configure an input delay for DIn.0.
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
4
21