Configuring/address space

4.9 Explanation of parameters

4.9
Explanation of parameters
4.9.1

Channel configuration

Channel configuration
This parameter is used to specify whether both channels are to be connected in parallel.
Channel configuration
2 channels (2 A)
(default)
1 channel (4 A)
Note
High-speed output
The "High-Speed Output (0.1 A)" can only be selected for the channel configuration "2
Channels (2 A)".
128
Meaning
The two channels operate separately and each has a maximum output
current of 2 A.
The two channels are connected in parallel and operate as a logical
channel with a maximum output current of 4 A.
All parameter settings and operations that use the control interface
must use addresses with Channel 0. Feedback signals are only pro-
vided for Channel 0.
The control and feedback interface is limited to one channel only.
Channel 1 cannot be configured or operated.
Current measurement adds the measured values of both channels.
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)