Parameter - Siemens ET 200SP Manual

Technology module tm pulse 2x24v
Hide thumbs Also See for ET 200SP:
Table of Contents

Advertisement

4.9.5

Parameter

High-speed output (0.1 A)
Use this parameter to specify whether or not the respective digital output works as a fast
push-pull switch.
Option
Activated
Disabled
(default)
Note
Channel configuration
You can only select this parameter with the channel configuration "2 channels (2 A)".
Note
You cannot enable this parameter in the operating modes "PWM with DC motor" and "Pulse
width modulation PWM" with current control.
Function DI
By configuring a digital input, you specify which functions the digital input triggers at
switching.
You can select from the following options:
Function
Input
(pre-selected)
HW enable
Limit switch
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Meaning
The digital outputs work as fast push-pull switches and each can carry a
rated load current of 0.1 A. A push-pull switch is alternately switched to
DC 24 V and ground. This makes for very fast edges.
The digital outputs work as fast push-pull switches and each can carry a
rated load current of 2 A.
Meaning
No function is assigned to the respective digital input. The signal status of
the digital input can be read by the CPU by means of the feedback inter-
face.
The respective digital input is used as enable input for the output se-
quence.
The respective digital input is used as external limit switch for a DC motor
in the "PWM with DC motor" mode.
Configuring/address space
4.9 Explanation of parameters
133

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents