SINAMICS S120 at Technology CPU Entry ID: 21767896
Table 6-4 Adapting the message type
No.
1.
2.
3.
4.
V1.0
Instruction
Edition 10/28/05
Commissioning SINAMICS S120
Commissioning SINAMICS S120
Note
In the SIMATIC Manager, select
SINAMICS_S120 and double-click
this component in the right
window.
This starts S7T Config for
SINAMICS S120.
Establish the online connection to
SINAMICS S120 using the Speed
button.
Attention:
At this point, activating the online
connection via the menu is not
possible!
In the component SINAMICS_S120,
select and double-click
Configuration to open it.
In the list, set the message type
SIEMENS Telegram 105 for the
drive SERVO_02.
Check the setting for the drive
SERVO_03. The message type
SIEMENS Telegram 105 should be
set for both drives.