Install a circuit breaker to a AC distributor for the stable power. The capacity of
circuit breaker is 20 A. (Use UL Listed circuit breakers.)

Connecting Power Cable

Connecting RRH Power Cable
To connect RRH DC Power cable
Make sure you have the following items:
1
Table 27. Parts and Tools for connecting RRH DC Power Cable
Category
Description
Installation
AC/DC Convertor(or Site Rectifier) ~ RRH Power Port
Section
Cable
8 AWG × 2C
Bend Radius
Operation: 8 × OD
Connector
AC/DC Convertor
* Check specifications of rectifier output terminal per site and prepare fasteners when
connect RRH power cable to the site rectifier
RRH
Working Tools
 Cable Cutter
 Wire Stripper
 Compressor
 Heating Gun
 Nipper
Table 28. RRH DC Power Cable Connector Pin Map
Power Connector
Description
Pin No.
Pin 1
-48 V DC
Pin 2
RTN
* The color of the core wire can be changed according to the specification of the cable used.
RF4402d Series Installation Manual v1.0
Copyright © 2018, All Rights Reserved.
Chapter 3 Connecting Cables
Installation: 12 × OD
JONHON, Push Pull Type, CT48J-1502TSCBM-07
JONHON, Push Pull Type, CT48J-1502TSCBM-07
Color
White
Black