Connecting AC/DC Convertor Ground Cable
To connect AC/DC Convertor Ground Cable
Make sure you have the following items:
1
Table 26. Parts and Tools for connecting AC/DC Convertor Ground Cable
Category
Description
Installation Section
MGB~ AC/DC Convertor Ground Terminal
Cable
6 AWG × 1C
Bend Radius
8 × OD
Heat Shrink Tube
Ф 0.47 in. (12 mm)/Clear/1.96 in. (50 mm)
(Spec/Color/Length)
Pressure Terminal
MGB
Checking MGB specifications per site and preparing connecting parts
AC/DC
6 AWG, 2 Hole, Hole diameter:1/4 in. (6.4 mm), Hole spacing: 0.63 in. (16
Convertor
mm)
Fastener
MGB
Checking MGB specifications per site and preparing connecting parts
AC/DC
M6 × L14 SEMS (Hex. +)/2 EA
Convertor
Recommended
M6 SEMS
43 lbf·in
Torque Value
Working Tools
Cable Cutter
Wire Stripper
Crimping tool
Heating Gun
Nipper
Screw Driver ('+', No. 3)
Torque Driver (20~90 lbf·in.)
Screw Driver Bit ('+', No. 3)
For the pressure terminal or the cable, the UL Listed products or equivalent should
be used.
Ex) Manufacturer-Panduit
RRH: 6 AWG Pressure Terminal (LCD6-14A-L)
Install a ground cable from the MGB to the AC/DC convertor ground terminal.
2
RF4402d Series Installation Manual v1.0
Copyright © 2018, All Rights Reserved.
Confidential
Chapter 3 Connecting Cables
72