6.4 Wiring

Explosion risk - During assembly work, sparks can form and surfaces may
become excessively hot.
• Before assembly, make sure that there is not a potentially explosive
Warning
• For applications in potentially explosive atmospheres, observe the
Warning
Safety functions of EP-19xx modules can be impaired. When EP-19xx
modules are installed in the RSTi-EP station, observe the following points:
• Use wire-end ferrules in combination with flexible/multi-conductor
Warning
• Ensure that for safety inputs in the configuration without test pulses

6.4.1 Wiring of Modules with Standard Connectors

Wires with a cross section between 0.14 mm² and 1.5 mm² (AWG 26 – 16) can be connected.
The external dimensions of the crimped wire-end ferrules must conform with IEC‑60947-1.
RSTi-EP modules (except HD modules) and bus network adapters are equipped with the spring-style
connector system. Singlestrand and fine-strand lines with wire-end ferrules can be inserted without
the need for a tool.
Each cable must be the optimal length so the bending radii observe the manufacturer's
specifications.
Strip the insulation from the lines to a length of approx. 10 mm ± 1 mm (o.4 in ± 0.04 in), even
if you are using wire-end ferrules. If you use wire-end ferrules with plastic collars, strip the
wires to 12 mm ± 1 mm (o.5 in ± 0.04 in).
Connect all lines according to wiring diagram.
For the usage and handling of the spring-style system, refer to the section, Removing/Replacing
Cables.
GFK-2958E
atmosphere.
installation and construction requirements of EN 60079- 15 and/or
country-specific regulations.
Dangerous contact voltage:
• Carry out assembly and wiring work on the RSTi-EP station only when
the power supply is disconnected.
• Make sure that the place of installation (switch cabinet etc.) has been
disconnected from the power supply.
cables.
the cabling prevents external short circuits (refer to DIN EN ISO 13849-
2 Table D.4).
RSTi-EP User Manual
Chapter 6 Installation
323