0X1000 - 0X1006 Network Adapter Identifier; 0X1000 - 0X1006 Network Adapter Status; 0X1010 Process Image Length In Bits For The Output Modules; 0X1010 Process Image Length In Bits For The Input Modules - GE RSTi-EP User Manual

Standalone 1ghz programmable controller
Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

4.4.6 0x1000 – 0x1006 Network adapter Identifier
The identifier is the product designation: EPXMBE001 and EPXMBE101 as per Network adaptor
catalogue number.
4.4.7 0x1000 – 0x1006 Network adapter Status
Bit
Name
0
Summarized module diagnosis
1
Errorbit 1
2
Errorbit 2
3
Systembus error
4
Errorbit 4
5
Errorbit 5
6
I/O-Configuration error
7
Master configuration error
8
Errorbit 8
9
Errorbit 9
10
Force mode active
11
Errorbit 11
12
Errorbit 12
13
Voltage U
error
OUT
14
Voltage U
error
IN
15
Errorbit 15

4.4.8 0x1010 Process Image Length in Bits for the Output Modules

4.4.9 0x1010 Process Image Length in Bits for the Input Modules

4.4.10 0x1017 Register – Mapping Revision
Version of the register structure
4.4.11 0x1018 – 0x101B Collective Diagnostics Message for I/O Modules
If a diagnostic alarm is activated (register 0x1134) and there is a diagnostic message for a module, it
is indicated here with a set bit. A module's slot position corresponds to its position in the 64-bit data
field (minus passive modules without slot recognition). Example: 0x0000 0000 0000 0002 = There is a
diagnostic alarm for module 2.
Reading the module's diagnostic memory (0xAXXX) confirms the diagnosis and resets the
corresponding bit. In case of multiple diagnoses for one module, only the most up-to-date diagnosis
is displayed. The next diagnostic is then placed in a wait loop and only becomes active once the
current one has been confirmed.
GFK-2958E
Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
Meaning
A diagnosis is available on at least one module with diagnostics functionality.
Reserve bit 1, currently not used
Reserve bit 2, currently not used
Error on system bus. Communication with the connected modules is disrupted.
Reserve bit 4, currently not used
Reserve bit 5, currently not used
Differing configuration. The module list has changed. The list of configured
modules (reference module list 0x2800 – 0x287F) differs from the module list
detected by the network adapter (current module list 0x2A00 – 0x2A7F).
Master configuration error. The list of configured modules (reference module list
0x2800 – 0x287F) differs significantly from the module list detected by the
network adapter (current module list 0x2A00 – 0x2A7F). Process data cannot be
exchanged with the modules.
Reserve bit 8, currently not used
Reserve bit 9, currently not used
Force mode was activated via the web server. Forced channels do not exchange
data with the master.
Reserve bit 11, currently not used
Reserve bit 12, currently not used
Error in the supply voltage of outputs
Error in the supply voltage of system and inputs
Reserve bit 15, currently not used
RSTi-EP User Manual
88