22 Electrical installation

Installing power and ground cables

NOTICE
Waste inside the cabinet can cause damage or malfunction.
High voltages will be present in the terminal compartment. High voltages can cause
flashover between the electric potential of different conductors, and the electric potential
of a conductor and earth.
Therefore, a minimum clearance of 82 mm must be maintained between a conductor
and earth, and 110 mm between a conductor and the terminals of any other conductor.
Prepare the cable termination as illustrated in the figure below. The condutor screen
must be connected to be PE ground busbar. It is prohibited to cut off.
1
1
Outer cable sheath
Outer cable sheath
2
2
Entry plate
Entry plate
3
3
Conductor screen extension to be connected to PE
Conductor screen extension to be connected to PE
ground busbar
ground busbar
4
4
Heat-shrinkable termination
Heat-shrinkable termination
5
5
Sealing compound
Sealing compound