36 Fault tracing
Code
Warning
(hex)
A2B1
Overcurrent
A2B4
Short circuit
A3D0
Grid ridethrough
A5F4
Control unit battery The battery of the control
A7EE
Panel loss
Cause warning
Output current has
exceeded internal alarm
limit.
Short-circuit in motor
cable(s)
or motor.
Grid voltage is below the
internal threshold so the
drive
is operating in low voltage
ridethrough mode.
unit
is low.
Control panel or PC tool
selected as active control
location for drive has
ceased
communicating.
What to do
Check motor load.
Check acceleration times in parameter
group 23 Speed reference ramp (rpm
operation mode) or 28 Frequency
reference chain (Hz operation mode).
Also check parameters 46.01 Speed
scaling and 46.02 Frequency scaling.
Check motor and motor cable (including
phasing and delta/star connection).
Check there are no contactors opening
and closing in motor cable.
Check that the data in parameter group
99 Motor data corresponds to the motor
rating plate.
Check that there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check motor and motor cable for cabling
errors.
Check that there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check the transformer secondary
voltage.
Replace control unit battery. Refer to the
HW manual for instructions on battery
replacement.
This warning can be suppressed using
parameter 31.40.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
Replace control panel in mounting
platform.