Hart Communication Interface - Siemens SITRANS FC430 Operating Instructions Manual

Coriolis flowmeters with hart
Hide thumbs Also See for SITRANS FC430:
Table of Contents

Advertisement

3.5

HART Communication Interface

System communication
Table 3- 1
Manufacturer ID
Device type
HART protocol revision
Device revision
Note: Version numbers and other references shown above are typical or example values.
Device description files
Available EDD drivers:
● SIMATIC PDM
● FDT/DTM
● AMS suite
● 375 Field Communicator
The drivers can be downloaded here:
Download EDD drivers (http://www.siemens.com/flowdocumentation)
Configuration of the HART polling address
The HART address can be set either via hardware (DIP switch) or via software (HMI or
SIMATIC PDM).
The DIP switch is located on the transmitter cassette, see position
Transmitter exploded view (Page 34).
Figure 3-6
● Configuration via DIP switch (HW polling address)
Set 1 to 15 on the DIP switch if you wish to set a fixed (hardware-defined) HART polling
address (SW polling address will be ignored). The configured HW polling address can be
read via HMI in menu item 4.2.
● Configuration via HMI or SIMATIC PDM (SW polling address)
Disable the HW polling address by setting all switches to "OFF" on the HART DIP switch.
The device starts up with default slave address = 0. The SW polling address can be
changed to a value between 0 and 63 via HMI (menu item 4.1) or SIMATIC PDM
FC430 with HART
Operating Instructions, 05/2015, A5E03361511-AF
HART protocol identification data
42 (2A Hex)
34 (22 Hex)
7.2
2
HART slave address switch
3.5 HART Communication Interface
Manufacturer ID parameter
Device type parameter
HART protocol revision parameter
Device revision parameter
Description
in Figure 3-5
37