Precautions
■Device to be set in the refresh device setting
Whether remote output (RY) is refreshed or compulsorily cleared varies depending on the refresh device set for the remote
output (RY) in "Link Refresh Settings" under "Basic Settings" as described below:
• When Y is set, remote output (RY) is compulsorily cleared regardless of the module parameter.
• When a device other than Y, such as M and L, is selected, remote output (RY) is refreshed or compulsorily cleared
according to the setting.
Data link stop and restart
Data link can be stopped during debugging and other operations. Also, the stopped data link can be restarted.
If data link of a master station is stopped, data link is stopped in the entire system. ( Page 110 Stopping and restarting
data link)
Remote I/O station points setting
When the master station is in the remote net Ver.2 mode or remote device net Ver.2 mode, the number of refresh points with a
remote I/O station can be selected from 8 points, 16 points, and 32 points. Changing the number of points can save the areas
of the refresh device in a CPU module. (In modes other than the remote net Ver.2 mode and remote device net Ver.2 mode,
only 32 points per station can be selected.)
When the number of remote I/O station
points is set
CPU module
Master station
Remote output (RY)
Station
No.2
Station No.3
Y
Station No.4
·
When the number of remote I/O station
points is not set
CPU module
Master station
Remote output (RY)
Station No.1
Station No.2
Y
Station No.3
Station No.4
Remote I/O station
(station No.: 1,
number of occupied
stations: 1)
Station
Y07 to Y00
No.1
8-point output module
Remote I/O station
(station No.: 1,
number of occupied
stations: 1)
Y07 to Y00
8-point output module
Remote I/O station
Remote I/O station
(station No.: 2,
(station No.: 3,
number of occupied
number of occupied
stations: 1)
stations: 1)
Y07 to Y00
Y0F to Y00
8-point output module
16-point output module
Remote I/O station
Remote I/O station
(station No.: 2,
(station No.: 3,
number of occupied
number of occupied
stations: 1)
stations: 1)
Y07 to Y00
Y0F to Y00
8-point output module
16-point output module
Remote I/O station
(station No.: 4,
number of occupied
stations: 1)
Y0F to Y00
Y1F to Y10
32-point output module
Remote I/O station
(station No.: 4,
number of occupied
stations: 1)
Y0F to Y00
Y1F to Y10
32-point output module
1 FUNCTIONS
39
1.1 Cyclic Transmission
1