■Points per module and per system
For the points, refer to the table of the performance specifications in the following manual.
 MELSEC iQ-R CC-Link System Master/Local Module User's Manual (Startup)
In CC-Link, increasing the number of occupied stations can increase the number of points per module. The number of
occupied stations is set for each slave station.
Item
Description
Number of
The number of points is increased by increasing the station numbers occupied per module.
Occupied
Note that the number of slave stations that can be connected to a CC-Link system is decreased because one module occupies the station
Stations
numbers for multiple modules.
■Data transfer between RX, RY, RWr, and RWw and a device in a CPU module
To perform auto transfer using the module parameters in an engineering tool, setting a refresh device in "Link Refresh
Settings" under "Basic Settings" can automatically transfer data between RX, RY, RWr, and RWw in a master/local module
and a device in a CPU module.
To perform transfer using a program, use a module access device (Un\G) and FROM/TO instructions to transfer data
between the buffer memory areas in a master/local module and a device in a CPU module.
Address
Hexadecimal
E0H to 15FH
160H to 1DFH
1E0H to 2DFH
2E0H to 3DFH
■Storage locations of RX, RY, RWr, and RWw
Areas are assigned by 32 points in the order of station number to the remote input (RX) and remote output (RY) ( Page
142 Remote input (RX) and remote output (RY)).
To the remote register (RWr and RWw), areas are assigned by four points in the order of station number. ( Page 144
Remote register (RWw) and remote register (RWr))
Decimal
224 to 351
352 to 479
480 to 735
736 to 991
Item
Remote input (RX)
Remote output (RY)
Remote register (RWw)
Remote register (RWr)
Reference
Page 142 Remote input (RX) and
remote output (RY)
Page 144 Remote register (RWw)
and remote register (RWr)