Mitsubishi Electric MELSEC iQ-R Series User Manual page 163

Melsec iq-r cc-link system master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
Description
SW005D
Forced master
Stores whether the forced master switching instruction using SB000C has been
switching
normally completed.
instruction result
0: Normal
Values other than 0:Error code ( Page 123 List of Error Codes)
SW005F
Remote device
Stores whether the initialization procedure registration instruction using SB000D
station
has been normally completed.
initialization
0: Normal
procedure
Values other than 0:Error code ( Page 123 List of Error Codes)
registration
instruction result
SW0060
Mode setting
Stores the mode setting status.
status
0: Online (remote net mode)
1: Online (remote I/O net mode)
2: Offline
3: Line test 1
4: Line test 2
6: Hardware test
C: Online (remote device net mode)
SW0061
Station number
Stores the current own station's station number.
of own station
0: Master station
1 to 64:Local station
SW0062
Module
Stores the module operation setting configured using the parameter.
operating status
b15b14b13
0
SW0064
Number of
Stores the set number of retries upon an abnormal response.
retries
1 to 7 (time)
information
SW0065
Number of
Stores the set number of automatic return stations in one link scan.
automatic return
1 to 10 (station)
stations
SW0067
Parameter
Stores the information of "Setting Method of Basic/Application Settings" under
information
"Parameter Setting Method" in "Required Settings".
0H:Parameter editor
3H:Program
SW0068
Parameter
Stores whether the parameters have been correctly set.
status of own
0: Normal
station
Values other than 0:Error code ( Page 123 List of Error Codes)
b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0
1
0
0
0
Station type
0: Master station/local station
1: Standby master station
Master station duplex function
0: Disable
1: Enable
Input data from data link faulty station
0: Clear
1: Hold
Number of occupied stations
00: 1 station occupied
10: 2 station occupied
11: 3 station occupied
01: 4 station occupied
Setting Method of Basic/Application Settings
0: Parameter Editor
1: Program
Output mode upon CPU STOPcase of
programmable controller CPU STOP
0: Refresh to remote output (RY)
1: Send 0 data to remote output (RY)
Extended cyclic setting
00: Single
01: Double
10: Quadruple
11: Octuple
Station-based block data assurance
0: Disable
1: Enable
Appendix 5 List of Link Special Register (SW) Areas
Availability (: Available, : Not
available)
Online
Offline
Master
Local
station
station
APPX
A
161

Advertisement

Table of Contents
loading

Table of Contents