Mitsubishi Electric MELSEC iQ-R Series User Manual page 161

Melsec iq-r cc-link system master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
Description
SW0009
Monitoring time
Sets monitoring time when dedicated instructions are used.
setting
Default: 10 (seconds) (value = 0)
Setting range: 1 to 360 (seconds)
If a value outside the range is set, the monitoring time will be 360 seconds.
When SW000B is set, the time until a dedicated instruction fails is as follows:
(Number of retries + 1)  monitoring time
SW000A
CPU monitoring
Sets the monitoring time of CPU response when the CPU module is accessed
time setting
through transient transmission.
Default: 90 (seconds) (value = 0)
Setting range: 1 to 3600 (seconds)
If a value outside the range is set, the monitoring time will be 3600 seconds.
SW000B
Dedicated
Sets the number of retries of when dedicated instructions are used.
instruction retry
Default: 0 (No retry)
count setting
Setting range: 0 to 7 (time)
If a value outside the range is set, the number of times will be 7.
SW0014
Specification of
Specifies a station where an initial processing is performed using the information
to
remote device
registered by the initialization procedure registration using an engineering tool.
SW0017
station to be
0: Initial processing not performed
initialized
1: Initial processing performed
SW0014
SW0015
SW0016
SW0017
The stations need not be set by the number of occupied stations.
Error invalid stations, reserved stations, station with the end station number, and
stations later than that are excepted.
SW0020
Module status
Stores the communication status between the master/local module and CPU
module.
0: Normal
Values other than 0:Error code ( User's manual for the CPU module used)
SW0041
Data link restart
Stores whether the data link restart instruction using SB0000 has been normally
result
completed.
0: Normal
Values other than 0:Error code ( Page 123 List of Error Codes)
SW0043
Refresh
Stores whether the refresh instruction at standby master switching has been
instruction at
normally completed.
standby master
0: Normal
switching result
Values other than 0:Error code ( Page 123 List of Error Codes)
SW0045
Data link stop
Stores whether the data link stop instruction using SB0002 has been normally
result
completed.
0: Normal
Values other than 0:Error code ( Page 123 List of Error Codes)
SW0049
Temporary error
Stores whether the temporary error invalid station specification has been
invalid station
normally completed.
specification
0: Normal
result
Values other than 0:Error code ( Page 123 List of Error Codes)
SW004B
Temporary error
Stores whether the temporary error invalid station setting has been normally
invalid station
canceled.
specification
0: Normal
cancel result
Values other than 0:Error code ( Page 123 List of Error Codes)
SW004D
Line test result
Stores the result of a line test.
0: Normal
Values other than 0:Error code ( Page 123 List of Error Codes)
SW0057
Master station
Stores whether a master station duplication error cancel request has been
duplication error
normally completed.
cancel result
0: Normal completion
Values other than 0:Error code ( Page 123 List of Error Codes)
to
b15
b14
b13
b12
16
15
14
13
to
32
31
30
29
to
48
47
46
45
to
64
63
62
61
to
1 to 64 in the table indicate station numbers.
Availability (: Available, : Not
available)
Online
Master
station
b3
b2
b1
b0
4
3
2
1
20
19
18
17
36
35
34
33
52
51
50
49
Appendix 5 List of Link Special Register (SW) Areas
Offline
Local
station
APPX
159
A

Advertisement

Table of Contents
loading

Table of Contents