ABB i-bus KNX Product Manual page 65

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
With the Yes: ... options, the following parameters appear:
Using the following parameters, further communication objects and their associated functions can be
enabled for the output of the DLR/S:
Enable communication objects:
"Conflict DALI"
Options:
There is a DALI conflict if the assignment of DALI devices stored in the DLR/S diverge from the actual
group assignment in the DALI line.
No: The communication object Conflict DALI is not enabled.
Yes: The communication object Conflict DALI is enabled. As soon as there is a conflict, this is
indicated by the value 1 in the communication object Conflict DALI. The following parameter appears:
Send
Options:
After a change
On request
After a change or request
After a change: The status is sent via the communication object after a change.
On request: The status is sent after a request by the communication object Request status
values.
After a change or request: The status is sent via the KNX when the status changes or the
status is requested via the communication object Request status values.
Value for for different brightness
states at the output
Options:
Average brightness of all lamps in the output
Highest brightness of all lamps in the output
Lowest brightness of all lamps on the output
This parameter defines the status to be sent if devices with different states are present on the
output.
Average brightness of all lamps in the output: The average brightness of all the DALI devices
(not the lighting groups) is sent as the status of the output on the KNX. Thus, a lighting group
with many DALI devices has a higher weighting in the calculation of the average brightness.
Highest brightness of all lamps in the output: The highest brightness value of the DALI devices
is taken as the status of the output sent on the KNX.
Lowest brightness of all lamps on the output: The lowest brightness value of the DALI devices
is taken as the status of the output sent on the KNX.
No
Yes
DLR/S 8.16.1M | 2CDC 507 100 D0202 63