Communication Objects General - ABB i-bus KNX Product Manual

Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.3.2

Communication objects General

No.
0
This communication object is enabled if, in the
operation" cyclically is set with the Yes option.
In order to monitor the presence of the DLR/S on the KNX at regular intervals, a monitoring telegram can be sent cyclically
on the KNX.
1
Manual operation can be enabled or disabled via this communication object.
Telegram value:
With disabled manual operation, it is not possible to switch the connected DALI devices manually via the DLR/S.
Furthermore, the Detect devices function cannot be implemented manually using the
At the same time, the status of manual operation can be read via this communication object, disabled (1) and enabled (0)
and/or sent on the KNX. The value of the communication object is sent on a change, at KNX voltage recovery, after a
download and on request.
With disabled manual operation, pressing the Manual operation button has no effect. The yellow Manual operation LED
flashes as long as the Manual operation button is pressed.
After download and KNX voltage recovery, the blocking of manual operation is removed.
2
The communication object is enabled if, in the
selected via the parameter Enable automatic DALI addressing with the No option.
Using this communication object, the internal function of the DLR/S is recalled, the DALI device addressing is verified and a
DALI address assigned if necessary.
Telegram value:
When the address assignment is recalled, the DLR/S verifies the DALI addresses. DALI devices without an address
receive a DALI address. DALI addresses that are assigned twice are removed.
124 2CDC 507 100 D0202 | DLR/S 8.16.1M
Function
In operation
Block manual operation/Status
0 = Manual operation is enabled
1 = Manual operation is disabled
Trigger DALI addressing
0 = DALI address assignment not initiated
1 = DALI address assignment is recalled once
Object name
General
Parameter window
General, page 43, the parameter Send object "In
General
General
Parameter window
General, page 43, automatic address assignment is
Data type
Flags
1 bit
C, T
DPT 1.002
1 bit
C, R, W, T
DPT 1.003
button.
1 bit
C, W
DPT 1.003