External Connections - GE 239 Instruction Manual

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

MANUAL PART NO.
1601-00XX-D4
2.1.3

External Connections

CT ROW
1
Phase A CT 5A
2
Phase A CT 1A
3
Phase A CT COM
4
Phase B CT 5A
5
Phase B CT 1A
6
Phase B CT COM
7
Phase C CT 5A
8
Phase C CT 1A
9
Phase C CT COM
10
Ground CT 5A
11
Ground CT 50:0.025
12
Ground CT COM
2–16
Courtesy of NationalSwitchgear.com
Table 2–1: Firmware/manual Revisions Table
FIRMWARE
VERSION
2.3x
Signal wiring is to box terminals that can accommodate wire as large as 12 gauge. CT
connections are made using #8 screw ring terminals that can accept wire as large as 8
gauge (see FIGURE 2–3: Typical Wiring Diagram on page 2–18). A minimal configuration will
include connections for control power, phase CTs and the trip relay. Other features can be
wired as required. Considerations for wiring each feature are given in the sections that
follow.
Table 2–2: External Connections
SIGNAL LOWER ROW
13
Safety ground
14
Filter ground
15
RS485 A+
16
RS485 B–
17
RS485 ground
18
Analog out +
19
Analog out –
20
Analog out shield
21
Thermistor in +
22
Thermistor com
23
Trip NO
24
Trip COM
25
Trip NC
26
Alarm NO
27
Alarm COM
28
Alarm NC
29
Auxiliary NO
30
Auxiliary COM
31
Auxiliary NC
32
Service NO
33
Service COM
CHAPTER 2: INSTALLATION
MANUAL PART NO.
1601-00XX-DB
SIGNAL UPPER ROW
36
Control live (+)
37
Control neutral (–)
38
Sw com
39
Sw com
40
Sw com
41
Sw com
42
Sw com
43
Access sw +
44
Restart sw +
45
Reset sw +
46
Option 1 sw +
47
Option 2 sw +
48
RTD shield
49
RTD1 hot
50
RTD1 comp
51
RTD1 ret
52
RTD2 hot
53
RTD2 comp
54
RTD2 ret
55
RTD3 hot
56
RTD3 comp
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
FIRMWARE
VERSION
2.7x

Hide quick links: