Note
1–12
Courtesy of NationalSwitchgear.com
Transients: .........................................................ANSI C37.90.1 Oscillatory 2.5 kV / 1 MHz; ANSI C37.90.1
Impulse Test:.....................................................IEC 255-5 0.5 Joule 5 kV
Voltage Deviation: .........................................IEC 61000-4-11
RFI:.........................................................................50 MHz/15 W Transmitter
EMI:........................................................................C37.90.2 Electromagnetic Interference @ 150 MHz and
Static: ..................................................................IEC 801-2 Static Discharge
Humidity: ............................................................95% non-condensing
Temperature:....................................................–10°C to +60°C ambient
Environment: ....................................................IEC 68-2-38 Temp/Humidity Cycle
Dust/Moisture: .................................................NEMA 12/IP53
PACKAGING
Shipping Box:....................................................8½" × 6" × 6" (L × H × D)
Ship Weight:......................................................5 lbs. / 2.3 kg
CERTIFICATION/COMPLIANCE
ISO: ........................................................................Manufactured under an ISO9001 recognized program
UL:..........................................................................E83849 UL listed for the USA and Canada
Specifications subject to change without notice.
Fast Rise 5 kV / 10 ns; Ontario Hydro A-28M-82; IEC255-4
Impulse/High Frequency Disturbance
Class III Level
450 MHz, 10 V/m
215 mm × 152 mm × 152 mm
(L × H × D)