CHAPTER 4: PROGRAMMING
4.2

S1: 239 Setup

SETPOINT
MESSAGE L
MESSAGE M
MESSAGE L
MESSAGE M
MESSAGE L
MESSAGE M
MESSAGE L
MESSAGE M
MESSAGE L
MESSAGE M
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
Settings to configure the 239 are entered here. This includes user preferences, RS485
communication port, loading of factory defaults, and user programmable messages.
]] SETPOINTS
]] S1 239 SETUP
MESSAGE 4
] PREFERENCES
]
MESSAGE 3
MESSAGE s
t
MESSAGE 4
] ANALOG OUTPUT
]
MESSAGE 3
MESSAGE 4
] RS485 SERIAL PORT
]
MESSAGE 3
MESSAGE 4
] DEFAULTS
MESSAGE 3
SEE NEXT PAGE
SETPOINT
]] SETPOINTS
]] S2 SYSTEM SETUP
TEMPERATURE DISPLAY
IN: CELSIUS
DEFAULT MESSAGE TIME
1.0 MINUTES
DEFAULT MESSAGE
BRIGHTNESS: 60%
BLOCK KEYPAD TRIP
RESET: NO
OVERLOAD PICKUP
DISPLAY ENABLE: YES
ANALOG OUTPUT TYPE:
MOTOR LOAD
ANALOG OUTPUT RANGE:
0-1 mA
SERIAL COMMS FAILURE
ALARM: OFF
SLAVE ADDRESS:
1
BAUD RATE:
9600 BAUD
PARITY: NONE
LOAD FACTORY
DEFAULTS? NO
CLEAR PRE-TRIP
DATA: NO
CLEAR STATISTICS
DATA: NO
DESIGNATES SETPOINTS
THAT ARE ONLY VISIBLE IF
RTD OPTION IS INSTALLED
Range: CELSIUS, FAHRENHEIT
Range: 0.1 to 5.0, OFF
Step: 0.1 min.
Range: 0 to 100
Step: 20%
Range: YES, NO
Range: YES, NO
Range : AVERAGE PHASE AMPS,
MOTOR LOAD, THERMAL CAPACITY,
RTD 1/2/3 TEMPERATURE
Range: 0-1 mA, 0-20 mA, 4-20 mA
Range: ON, OFF
Range: 1-255, Step 1
Range: 1200, 2400, 4800, 9600, 19200
Range: NONE, EVEN, ODD
Range: YES, NO
Range: YES, NO
Range: YES, NO
DESIGNATES SETPOINTS THAT
ARE ONLY VISIBLE IF ANALOG
OUTPUT OPTION IS INSTALLED
4–13