S2: System Setup - GE 239 Instruction Manual

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

4.3

S2: System Setup

SETPOINT
]] SETPOINTS
]] S2 SYSTEM SETUP
MESSAGE
MESSAGE
] CT INPUTS
]
MESSAGE
MESSAGE
] MOTOR DATA
]
MESSAGE
MESSAGE
] END OF PAGE S2
]
4–20
Courtesy of NationalSwitchgear.com
SETPOINT
]] SETPOINTS
]] S3 OUTPUT RELAYS
MESSAGE
PHASE CT PRIMARY:
OFF A
GROUND SENSING:
MESSAGE
OFF
GROUND CT PRIMARY:
100 A
NOMINAL FREQUENCY:
60 Hz
MESSAGE
MOTOR FULL LOAD
CURRENT: OFF
OVERLOAD PICKUP
MESSAGE
INHIBIT ≤ 1.00 x FLC
USE OVERLOAD PICKUP
INHIBIT ON: RUN
LOCKED ROTOR
CURRENT: 6.0 x FLC
SAFE STALL TIME
COLD: 10.0 s
HOT/COLD CURVE
RATIO: 85%
DISABLE STARTS:
NO
DESIGNATES SETPOINTS THAT
MUST BE PROGRAMMED BEFORE
THE "TRIP" OUTPUT WILL RESET
FIGURE 4–3: Setpoints Page 2 – System Setup
CHAPTER 4: PROGRAMMING
Range: 5 to 1500, OFF
Step: 5 A
Range: RESIDUAL, CORE BAL 50:0.025,
COR BAL X:5, OFF
Range: 5 to 1500
Step: 5 A
Range: 50, 60
Range: 1 to 1500, OFF; Step 1 (CT PRI SET > 50 A)
Range: 0.1 to 150.0, OFF; Step 0.1 (CT PRI SET
Range: 1.00 to 5.00; Step 0.05
Range: RUN, START, START & RUN
Range: 0.5 to 11.0; Step 0.1 x FLC
Range: 1.0 to 600.0; Step 0.1 s
Range: 5 to 100%; Step 1%
Range: NO, YES
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
50A)